Table8–7 Mul-statevalueobjects
Schedule object
The EZstat occupancy state is controlled from a standard BACnet schedule object. The occupancy state is stored in the
reference object binary value object OCC_SCHEDULE. The excepon schedule within the schedule object is represented in
the user interface as the holiday schedules.
Table 8-8 Schedule object
Operang states and modes—the binary and mulstate value objects represent operang condions in the EZstat.
Objects BV5 and BV36 are related to the schedule.
Table 8–6 Binary value objects
Value object Name Descripon
BV5 OCC_SCHEDULE Occupy Schedule
BV6 DAT_ENABLE DAT Enable
BV7 DAT_SENSOR DAT Sensor Present
BV9 FAN_NEED Call for Fan
BV10 COOL_HEAT_NEED Cooling or Heang needed
BV11 SPEED_UP Speed up Timers x15
BV13 OCCUPIED_FAN Fan On During Occupied Mode
BV14 FAN_STATUS Fan Proof
BV15 MOD_FAN_ACTION Modulang or Stepped Fan Acon
BV16 AUTO_FAN_RESET Reset Fan Back to Auto
BV18 CL_VLV_ACTION Normal Close/Normal Open
BV19 HT_VLV_ACTION Normal Close/Normal Open
BV20 COOL_STG_1 Cooling Stage 1
BV22 HEAT_STG_1 Heang Stage 1
BV28 LOCAL_OVRD Local Override Mode
BV36 STPT_HOLD Hold Temperature Setpoint
Value object Name Descripon
MSV1 OCCUPIED_MODE Occupied Mode
MSV2 SYSTEM_MODE Control Mode
MSV3 FAN_MODE Fan Auto‑Manual Mode
MSV4 AVAILABLE_SPEEDS Number of Fan Speeds Available
Object Name Descripon Object Reference
1 SCHED_1 Schedule #1
BV5
Loop objects
The BACnet PID loops are used for valve and fan modulaon, staging, economizer operaon, and reheat during
dehumidicaon. The proporonal and integral properes of the cooling and heang loops are available from the user
interface.