Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 17 of 36
Procedure Steps Display
Select a
commissioning
funcon
Access to the commissioning funcons always starts at the MAIN menu display.
Procedure Steps Display
Starng Display
1. Start at the temperature display.
2. Enter Password 2. The display changes to the MAIN menu display.
F
°
70
AUTO AUTO
Choose and set
the setpoints
1. From the MAIN menu, press either the or buon to select
SETPOINTS.
2. Press the Enter . The SETPOINTS menu opens.
3. Choose and set each of the following setpoints.
OCC COOL—The cooling setpoint that is used as the acve
setpoint when the system is occupied.
OCC HEAT—The heang setpoint that is used as the acve setpoint
when the system is occupied.
UNOCC COOL—The cooling setpoint that is used as the acve
setpoint when the system is un‑occupied.
UNOCC HEAT—The heang setpoint that is used as the acve
setpoint when the system is unoccupied.
MIN COOLING—The minimum cooling setpoint that a user can
select as the acve setpoint.
MAX HEATING—The maximum heang setpoint that a user can
select as the acve setpoint.
DIFFERENTIAL—The minimum value between the cooling or
heang setpoints. The EZstat will always maintain this dierence
between set points.
STBY OFFSET—A value used to calculate the standby setpoint.
The standby setpoint is calculated by adding or subtracng
the oset value to or from the value of the occupied setpoint.
(Applicable to BACnet systems only).
COOL DAT LIMIT* – A value used to control the discharge cooling
temperature.
HEAT DAT LIMIT* – A value used to control the discharge heang
temperature.
* Nailor Exclusive: The DAT is monitored by the control and will modulate
the valve according to the demand versus DAT setpoint
Back
Enter
Cncl
SETPOINT
OCC COOL
OCC HEAT
UNOCC COOL
UNOCC HEAT
MIN COOLING
MAX HEATING
DIFFERENTIAL
Back
Enter
Cncl
SETPOINT
OCC COOL
OCC HEAT
UNOCC COOL
UNOCC HEAT
MIN COOLING
MAX HEATING
DIFFERENTIAL
6.2 Sengthecommissioningsetpoints
The commissioning setpoints set the operaonal setpoints and limits for the EZstat. Seng commissioning setpoints
requires entering Password 2 which is described in the topic Enter the Commissioning mode.
Not all setpoints in the following procedure are applicable to all models of EZstat.
NOTE
NOTE